Vol. 48

Front:[PDF file] Back:[PDF file]
Latest Volume
All Volumes
All Issues
2016-04-27

Decreasing the Extremely Low-Frequency Electric Field Exposure with a Faraday Cage During Work Tasks from a Man Hoist at a 400 kV Substation

By Herkko Pirkkalainen, Jarmo Elovaara, and Leena Korpinen
Progress In Electromagnetics Research M, Vol. 48, 55-66, 2016
doi:10.2528/PIERM16021501

Abstract

Earlier studies have shown that the occupational exposure of electric fields at 400 kV substations can be higher than the low action level of 10 kV/m set by the Directive 2013/35/EU. One possibility for decreasing the occupational exposure is to surround the worker with a Faraday cage. The objective of the study was to investigate how effective a Faraday cage is in decreasing the ELF electric field exposure during work tasks from a man hoist at a 400 kV substation. First, we measured the electric field exposure while performing maintenance tasks from a man hoist. We then constructed a Faraday cage around the man hoist and measured the exposure again, with hopes that the exposure would be sufficiently reduced to create a safe working environment. The Faraday cage was constructed from a steel net 0.5 m in width with 19-mm meshes. The net was made of hotdip galvanized steel wire, 1.0 mm in diameter. The net and the man hoist were then grounded. The maximum electric field without the cage was 28.8 kV/m, and with the cage, it was 0.5 kV/m. The electric field, therefore, was decreased by 96.8-99.9%, validating the efficacy of Faraday cages.

Citation


Herkko Pirkkalainen, Jarmo Elovaara, and Leena Korpinen, "Decreasing the Extremely Low-Frequency Electric Field Exposure with a Faraday Cage During Work Tasks from a Man Hoist at a 400 kV Substation," Progress In Electromagnetics Research M, Vol. 48, 55-66, 2016.
doi:10.2528/PIERM16021501
http://www.jpier.org/PIERM/pier.php?paper=16021501

References


    1. Safigianni, A. and C. Tsompanidou, "Electric- and magnetic-field measurements in an outdoor electric power substation," IEEE Trans. Power Del., Vol. 24, No. 2, 38-42, 2009.
    doi:10.1109/TPWRD.2008.917690

    2. Joseph, W., L. Verlock, and L. Martens, "General public exposure by ELF fields of 150-36/11-kV substations in urban environment," IEEE Trans. Power Del., Vol. 24, No. 2, 642-649, 2009.
    doi:10.1109/TPWRD.2008.2002686

    3. Munteanu, C., V. Topa, A. Racasan, G. Visan, and I. T. Pop, "Computation methods and experimental measurements of the electric and magnetic field distribution inside high voltage substations," Int. Conf. Electromagnetics in Advanced Applications, 253-256, Torino, Italy, September 2009.

    4. Munteanu, C., G. Visan, I. T. Pop, V. Topa, E. Merdan, and A. Racasan, "Electric and magnetic field distribution inside high and very high voltage substations," 20th Int. Zurich Symposium on EMC, 277-280, Zurich, Switzerland, January 2009.

    5. Bräunlich, G. and R. Bräunlich, "Worst case evaluation of magnetic field in the vicinity of electric power substations," 20th Int. Zurich Symposium on EMC, 289-292, Zurich, Switzerland, January 2009.

    6. Tanaka, K., Y. Mizuno, and K. Naito, "Measurement of power frequency electric and magnetic fields near power facilities in several countries," IEEE Trans. Power Del., Vol. 26, No. 3, 1508-1513, 2011.
    doi:10.1109/TPWRD.2010.2078836

    7. Naito, K., Y. Mizuno, N. Matsubara, and N. Yamazaki, "Power frequency electric and magnetic fields around power facilities," Proc. Int. Conf. Electrical Engineering, 242-245, Matsue, Japan, 1997.

    8. Ando, T., K. Naito, Y. Mizuno, M. Moreno, G. Aponte, H. Cadavid, and M. Castro, "Power frequency electric and magnetic fields measurements in Japan and Latin-American Countries," EMC Europe, paper No. OE-5, Sorrento, Italy, September 2002.

    9. Sirait, K. T., P. Pakphan, B. Angorro, K. Naito, Y. Mizuno, K. Isaka, and N. Hayashi, "Report of 1995-1996 joint research on electric and magnetic field measurement in Indonesia," 12CEPSI, Vol. 8, 193-199, Pattaya, Thailand, November 1998.

    10. Moreno, M., K. Naito, and Y. Mizuno, "Report of joint research on power frequency electric and magnetic fields measurements in Mexico," 5th Int. Conf. Live Maintenance, paper No. 72, Session 11, May 2000.

    11. Sangkasaad, S., P. Pruksanubarn, V. Ngampradit, K. Naito, Y. Mizuno, and N. Matsubara, "Report of 1977 joint research on the electric and magnetic field measurement in Thailand RVP-AI/99,", 140-145, 1999.

    12. Ando, T., K. Naito, M. Katsuragawa, K. Takenaka, and Y. Mizuno, "Measurement of power frequency electric and magnetic fields around 500-kV power facilities in U.S.A.," Proc. Nat. Convention Rec. Inst. Elect. Eng. Jpn., 314-315, Nagoya, Japan, 2001.

    13. Int. Comm. Non-Ionizing Radiation Protection, "Guidelines for limiting exposure to time-varying electric, magnetic and electromagnetic fields (up to 300 GHz)," Health Phys., Vol. 74, No. 4, 494-522, 1998.

    14. European Parliament and Council of the European Union, "Directive 2013/35/EU of the European Parliament and of the council on the minimum health and safety requirements regarding the exposure of workers to the risks arising from physical agents (electromagnetic fields) (20th individual directive within the meaning of Article 16 (1) of directive 89/391/EEC) and repealing directive 2004/40/EC," Official Journal of the European Union, Vol. 21, 2013.

    15. Korpinen, L., J. Elovaara, and H. Kuisti, "Evaluation of current densities and total contact currents in occupational exposure at 400 kV substations and power lines," Bioelectromagnetics, Vol. 30, 231-240, 2009.
    doi:10.1002/bem.20468

    16. Cameron, G. W., P. S. Bodger, and J. J. Woudberg, "Incomplete Faraday cage effect of helicopters used in platform live-line maintenance," IEEE Proc. - Gener. Transm. Distrib., Vol. 145, No. 2, 145-148, 1998.
    doi:10.1049/ip-gtd:19981787

    17. Zakaria, N. A., R. Sudirman, and M. N. Jamaluddin, "Electromagnetic interference effect from power line noise in electrocardiograph signal using Faraday cage," 2nd Int. Conf. Power and Energy, 666-671, Johor Baharu, Malaysia, December 2008.

    18. Helhel, S. and S. Ozen, "Assessment of occupational exposure to magnetic fields in high-voltage substations (154/34.5 kV)," Radiat. Prot. Dosimetry, Vol. 128, No. 4, 454-570, 2008.

    19. Ozen, S., S. Helhel, and H. F. Carlak, "Occupational exposure assessment of power frequency magnetic field in 154/31.5 kV electric power substation in Turkey," PIERS Proceedings, 1440-1443, Prague, July 6-9, 2015.

    20. Ozen, S., E. G. Ogel, and S. Helhel, "Residential area medium voltage power lines; Public health, and electric and magnetic field levels," Gazi Uni. Jour. Sci., Vol. 26, No. 4, 573-578, 2013.

    21. Helhel, S. and S. Özen, "Evaluation of residential exposure to magnetic field produced by power lines near homes and working environments," Int. Jour. Engineering and Applied Sciences, Vol. 2, No. 3, 1-10, 2010.